USER’S GUIDE
InRow RC ACRC100 Series
9
2. Enter the user name and password (by default, apc and apc for an
Administrator, or device and apc for a Device-Only User).
SSH for high-security access. If you use the high security of SSL for the Web
interface, use Secure SHell (SSH) for access to the control console. SSH encrypts user
names, passwords,and transmitted data.
The interface, user accounts, and user access rights are the same whether you access
the control console through SSH or Telnet, but to use SSH, you must first configure
SSH and have a SSH client program installed on your computer.
Local access to the control console
You can use a local computer that connects to the InRow RC through the serial port on
the controller board that is on the electrical panel (connector J2) of the unit.
1. Select a serial port at the local computer and disable any service that uses that
port.
2. Use the supplied RS-232 configuration cable (APC part number 940-0103A) to
connect the selected port to the serial port at the InRow RC (use the DB-9
connector on the front of the electrical panel).
3. Run a terminal program (such as HyperTerminal) and configure the selected
port for 9600 bps, 8 data bits, no parity, 1 stop bit, and no flow control. Save the
changes.
4. Enter the user name and password for the access desired (Administrator or
Device-Only User).
If the InRow RC uses a non-default port number (between 5000
and 32768), you need to include a colon or a space (depending
on your Telnet client) between the IP address and the port
number.
To access the serial port, remove the front panel and lower air filter of
the InRow RC.